Petroleum Safety Significant Incident Report No. 01/2009 - Side-boom contacts power line

Last updated: 21 November 2024

A side-boom was working in tandem with a second side-boom to move a pipeline segment into a trench. The working side of the trench had been elevated by placing the spoil on that side. The segment movement was anticipated to be the last of the day and the operators began the move without a spotter.

The side-boom either contacted, or approached close enough to cause an arc from, a 22 kV power line. The power line broke. The live end ignited a small grass fire and the dead end came to rest on the side-boom.

The operator left the side-boom shortly after the power line broke and while the dead end of the power line was still in contact with the side-boom.

The trench had only been recently excavated and catenary markers to show the power line’s location and safe working distance had been removed for excavation.